P
Peggy HuynhAug 22, 2025
What to do if my HTP Elite EL-80 Boiler displays Fault Code F09?
- AAlyssa ChristianAug 22, 2025
If your HTP Boiler shows fault code F09, it means the boiler attempted to ignite four times during a single heat call but failed. Here's what to do: 1. Check for a spark at the igniter through the observation window. 2. If there's no spark, ensure the spark electrode gap is properly set to .196” (5.0 mm ± 1mm). 3. Remove any corrosion from the spark electrode and flame rectifier probe. 4. If there is a spark but no flame, verify the gas supply to the boiler. 5. If there is a flame, inspect the flame sensor. 6. Inspect for any flue or condensate blockages.