lp-666 Rev. 003 Rel. 001 Date 2.25.20
18
Table 5 - Pressure Drop at Various Temperature Rises
In addition, the boiler heat exchanger has a minimum total water ow rate that must be taken into account when sizing the circulator.
Pressure drops are listed in the table below.
The boiler heat exchanger does have a pressure drop which must be considered in system design.
G. Circulator Sizing
Table 6 - Multiple Boiler Manifold Piping - NOTE: Table based on water velocity less than Five (5) feet per second.
The chart below represents the combined ow rates and pipe sizes when using multiple boilers to design the manifold system for the primary
circuit. To size, simply add up the number of boilers and the required ow rates for the system design temperature.
Example: (5) 1000 boilers with a design of 30
o
F temperature rise with each boiler having an individual ow rate of 64 GPM. To correctly size
the manifold feeding these boilers, you would need a pipe size of 6”.
Model
20
o
F 30
o
F 40
o
F
GPM Ft / Hd GPM Ft / Hd GPM Ft / Hd
400 39 12.0 26 7.2 19 4.0
500 48 11.4 32 5.4 24 3.2
650 63 11.5 42 6.2 31 4.0
800 77 12 52 6 39 3
1000 96 14.0 64 7 48 4.7
1500 146 16 97 7.6 73 4.7
2000 194 21 129 11.5 97 6.7
Model
Number of Units and Recommended Common Header Pipe Sizes in Inches
2 3 4 5 6 7 8
400 3 3 4 4 5 5 5
500 3 4 4 5 5 5 6
650 4 4 5 5 6 6 6
800 4 5 5 6 6 8 8
1000 4 5 6 6 8 8 8
1500 5 6 8 8 8 10 10
2000 6 6 8 8 10 10 12
ELX-2000
ELX-1500
ELX-1000
ELX-800
ELX-650
ELX-500
ELX-400
0
5
10
15
20
25
30
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210
Pressure Loss (Feet of Head) +/- 10%
Flow Rate (GPM)
ELX-400 ELX-500 ELX-650 ELX-800 ELX-1000 ELX-1500 ELX-2000
Figure 10 - Pressure Drop through the Boiler