J. Programming Installer Settings
Installer Setting Program Access
NOTE: Programming the boiler control is not possible when the boiler is ring. Make sure any input which can create a demand on the boiler,
such as the tank thermostat, is turned o, so the boiler will remain idle to allow programming.
NOTE: To change Installer Settings enter Access Code 925 when prompted.
Installer Setting Program Navigation
Use the touch screen sliders or input prompts to change the Installer settings. Press SAVE to store changes. Press NEXT to advance to the next
screen, and PREVIOUS to go back a screen. The following are the Installer settings that can be programmed into the control.
Installer - Outdoor Reset Curve Screen
The Outdoor Reset Curve Screen provides the installer with a number of sliders to quickly and eciently set the outdoor reset curve. These
settings can also be found in the Installer - Installer Menu. These settings are as follows:
OUTDOOR RESET CURVE
System Setting
SAVE
NEXT
OUTDOOR TEMP
68ºF
122ºF
32ºF
0
50ºF
190ºF
Shutdown
BOOST TIME
190ºF I 5ºF
95ºF I 68ºF
762
-40ºF 110ºF
0min
S
E
T
P
O
I
N
T
Installer - Outdoor Reset Curve Screen
Press SAVE to
save the Outdoor
Reset Curve
settings
Press NEXT to
advance to the
Installer Menu
Screens
Slider 3 - Set the Outdoor Shutdown Temperature
Slider 4 - Set the Boost Time
Use the Sliders
to set the
Outdoor Reset
Curve
Slider 1
Maximum
Supply
Temperature
and
Minimum
Outdoor
Temperature
Slider 2
Minimum Supply
Temperature
and
Maximum
Outdoor
Temperature
Figure 46 - Installer - Outdoor Reset Curve Screen - NOTE: An Outdoor Sensor Must Be Used When Setting an Outdoor Reset Curve
Setting Description
Slider 1
Maximum Supply Temp 180
o
F
and
Minimum Outdoor Temp 5
o
F
Sets the maximum design supply temperature based on the minimum outdoor design temperature.
Default: 180
o
F (Range: 77
o
F to 190
o
F).
Sets the minimum outdoor design temperature for the system. Default: 5
o
F (Range: -42
o
F to 32
o
F).
Slider 2
Minimum Supply Temp 95
o
F
and
Max Outdoor Temp 68
o
F
Sets the design supply water temperature based on the maximum outdoor design temperature. Default:
95
o
F (Range: 32
o
F to 190
o
F).
Sets the maximum outdoor design temperature for the system design. Default: 68
o
F (Range 32
o
F to 190
o
F).
Slider 3
Outdoor Shutdown Temp
Sets the outdoor temperature where the boiler will ignore central heating demands. Default: 68
o
F (Range
41
o
F to 122
o
F).
Slider 4
Boost Time
Boost Time temporarily overrides the Outdoor Reset Curve, bringing the boiler up to the maximum
setpoint to satisfy a thermostat call in less time. For example, if 6 minutes is selected, and there has been a
thermostat call for 6 minutes, the boiler will override the Outdoor Reset Curve and boost to the maximum
setpoint until the call for heat is satised. The setpoint will stay at max for 6 minutes from the time the
thermostat opens. After the 6 minutes have elapsed the setpoint will return to the Outdoor Reset Curve.
Factory Default: 0 min (Range: 0-762 min in increments of 6 minutes.)
Table 16 - Installer - Outdoor Reset Curve Screen