Category Default Value Value Range Setting
Disable, Critical alarm, Minor alarm, Bypass mode, Battery mode,
Low batt. volt., Low battery SOC, Abnormal mains, Sys maint
breaker enable, Sys outp breaker enable, Maint. breaker closed, No
power supplied, Mains supplies power, ECO mode, Battery test, Batt.
Volt. Below Thres
Sys outp breaker enable
Disable
Disable, Critical alarm, Minor alarm, Bypass mode, Battery mode,
Low batt. volt., Low battery SOC, Abnormal mains, Sys maint
breaker enable, Sys outp breaker enable, Maint. breaker closed, No
power supplied, Mains supplies power, ECO mode, Battery test, Batt.
Volt. Below Thres
Sys outp breaker enable
Disable Disable, Enable Enable
Disable Disable, Enable Enable
Disable Disable, Enable Disable
Depends on the actual model. 0kVA–5000kVA 0
0 0%–100% 0
Disable Disable, Enable Disable
200% 50%–200% 200%
400 380, 400, 415 400
380V
220 209.0–231.0 /
400V
230 218.5–241.5 230
415V
240 228.0–252.0 /
50Hz 50Hz, 60Hz 50Hz
0.6Hz/s 0.1Hz/s–2.0Hz/s 0.6Hz/s
380V
15% +10%, +15%, +20%, +25% /
400V
15% +10%, +15%, +20% 15%
415V
10% +10%, +15% /
-20%
-10%, -15%, -20%, -30%,
-40%, -50%, -60%
-20%
±2Hz ±0.5Hz–±6Hz ±2Hz
English
English, Chinese, Spanish, Dutch, French, German, Italian, Polish,
Portuguese, Russian, Swedish, Turkish, Japanese
English
000001 / Default Value
Enable Disable, Enable Enable
PDC maintenance breaker [MT]
D.G. power limiting (kVA)
D.G. charger power ratio (%)
Input cur. limiting ratio(%)
Output volt.
adjustment(V)
Output freq. track rate(Hz/s)
password complexity check
Bypass frequency range (Hz)