23
1. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
Powering On Loads
7.5
Turn the output disconnector of the isolation transformer to ON.
Turn the AC output circuit breaker in the ICC cabinet to ON.
Tap the start/stop button on the MDU main menu of the ICC cabinet to
control the system output. Wait about 4 to 5 minutes until the load starts to
power on.
Setting Parameters for the Lithium Battery Cabinet
7.4
3. (For a parallel system) On the MDU of the master cabinet, choose System Info > Settings >
Basic Param, and set Transformer Cabinet SPD Fault Alm. Cond. to Close.
If the voltage of a single battery module is lower than the value of this parameter,
the battery module is automatically powered off. Set this parameter based on site
requirements.