SMU01A
User Manual
3 LCD Description
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
18
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
LVD2Voltage
43.2 V
LVD2Reconnect
Voltage
51.5 V
Others
Battery
Temperature
Very High
Action
Do Nothing
Battery High
Temperature
45°C
Battery Very
High
Temperature
53°C
Battery Low
Temperature
Point
C
Battery Very
Low
Temperature
10°C
Load HiTemp
Dis
NOTE
The menu is
displayed only in
ETP48150,
ETP4890, and
ETP4830
systems
Disable
LVD Setting
LVD1 Enabled
Disable
LVD2 Enabled
Enable
LVD2Mode
By Voltage
LVD2Voltage
43.2 V
LVD2Recon
Volt
51.5 V
Communication
Parameter
Host CommAddr
-
0
Host Baudrate
-
9600 bit/s
DHCP
Disable
Phone Number 1
Account 1