No. Parameter Description Remarks
11 Reactive power
change gradient
(%/s)
Species the change speed of the
inverter reactive power.
-
12 Plant active power
gradient (min/
100%)
Species the rate of active power
rise due to sunlight changes.
-
13 Average active
power ltering time
(ms)
Species the period of active
power rise due to sunlight
changes. This parameter is used
with Plant active power gradient.
-
14 Power factor Species the power factor of the
inverter.
-
15 Reactive power
compensation (Q/S)
Species the reactive power output
by the inverter.
-
16 Overfrequency
derating
If this parameter is set to Enable,
the active power of the inverter
will be derated according to a
certain slope when the grid
frequency exceeds the frequency
that triggers overfrequency
derating.
-
17 Frequency for
triggering
overfrequency
derating (Hz)
The standards of certain countries
and regions require that the
output active power of inverters be
derated when the power grid
frequency exceeds a certain value.
This parameter is
displayed when
Overfrequency derating
is set to Enable.
When setting this
parameter, ensure that
the following condition is
met: Frequency for
exiting overfrequency
deratingFrequency
for triggering
overfrequency derating
<
Cuto frequency of
overfrequency derating.
18 Frequency for
exiting
overfrequency
derating (Hz)
Species the frequency threshold
for exiting overfrequency derating.
19 Cuto frequency of
overfrequency
derating (Hz)
Species the frequency threshold
for cutting o overfrequency
derating.
20 Cuto power of
overfrequency
derating (%)
Species the power threshold for
cutting o overfrequency derating.
21 Power recovery
gradient of
overfrequency
derating (%/min)
Species the recovery rate of the
overfrequency derating power.
22 PF (U) voltage
detection ltering
time (s)
Species the time for ltering the
grid voltage in the PF-U curve.
-
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
Series
User Manual 7 Man-Machine Interactions
Issue 07 (2021-07-08) Copyright © Huawei Technologies Co., Ltd. 76

Table of Contents

Other manuals for Huawei SUN2000-215KTL-H0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-215KTL-H0 and is the answer not in the manual?

Huawei SUN2000-215KTL-H0 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-215KTL-H0
CategoryInverter
LanguageEnglish

Related product manuals