8
Possible Cause
Measures
The mains input power cable is
disconnected.
Check the input power cable.
The mains input power cable is
incorrectly connected to the UPS
output end.
Correctly connect the mains input
power cable to the UPS input
terminal.
and blink on the
The external or internal batteries
are incorrectly connected.
Check that all batteries are
connected correctly.
and blink on the
The UPS is overloaded.
Remove surplus load from the UPS
output end.
The UPS is overloaded and
supplying power to devices in
bypass mode.
Remove surplus load from the UPS
output end.
The UPS is overloaded server times
within a short period of time. The
UPS is locked in bypass mode and
loads are directly connected to the
main power source.
Remove surplus load from the UPS
output end, and then shut down
and restart the UPS.
Batteries are not fully charged.
Charge batteries for at least 5
hours and then check the battery
capacity. If the battery capacity is
still insufficient, contact the dealer.
Batteries are faulty.
Contact the dealer to replace
batteries.
8
Troubleshooting

Other manuals for Huawei UPS2000-A-1KTTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTL and is the answer not in the manual?

Huawei UPS2000-A-1KTTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A-1KTTL
CategoryUPS
LanguageEnglish

Related product manuals