the system has
no output, and
inverter startup
is prohibited.
inverter still
works properly,
but the system
cannot transfer
Possible cause: The bypass input
three
-phase sequence is incorrect.
Measure: Check that bypass input
power cables are correctly connected.
An alarm is
generated, and the
battery lifespan is
affected.
The configured number of
batteries is less than the actual
number.
The battery string charge voltage
exceeds the upper threshold.
Check battery parameter settings.
• Check the charger. When batteries
are disconnected, check whether
the charger voltage is normal. If
the charge voltage exceeds the
upper threshold, contact Huawei
technical support.
An alarm is
generated, and the
system may shut
down due to EOD.
Possible cause: The mains input is
abnormal. Battery discharge results in
a low battery voltage.
Measure: If possible, connect to the
mains power when the UPS is in non-
battery test state.
The UPS shuts
down.
The UPS transfers
to another working
mode or shuts
down.
The mains experiences
instantaneous high-
The output has special loads such
as inductive loads and rectification
The output has transformer loads
but the transformer mode is not
set.
After you rectify the fault, restart
the UPS.
Check whether the load type is
supported by the UPS.
Enable the transformer mode.