Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0012-01 BPS
neutral
loss
Minor Automa
tic
If the inverter has not
started and the batteries
are abnormal, the UPS
cannot work in inverter
mode. If the batteries are
normal, the UPS can work
in inverter mode.
If the inverter has started,
the UPS can work in
inverter mode properly.
Possible cause: The
bypass input neutral
wire is not connected.
Measures: Check that
bypass input power
cables are correctly
connected.
0014-01 Start
timeout
Critical Manual
/Power-
o
The UPS cannot be started. Possible causes:
The bypass load
exceeds the rated
inverter load.
An internal fault
occurs in the UPS.
Measures:
Reduce the output
load, manually clear
the alarm, and
restart the UPS.
Contact Huawei
technical support for
repair.
0020-01 Batt.
reverse
Critical Automa
tic
The power supply from the
UPS and system is not
aected.
Possible cause: Batteries
are reversely connected.
Measure: Check the
battery installation, and
reinstall the batteries.
0022-01 No
battery
Minor Automa
tic
The power supply from the
UPS and system is not
aected.
Possible causes:
Batteries are not
connected.
Batteries are not
securely connected.
Measures:
Connect batteries.
Check that batteries
are securely
connected.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 146