Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0040-04 Rectier
fault
Critical Manual
/Power-
o/
Automa
tic
The UPS shuts down.
The UPS transfers to another
working mode or shuts
down.
Possible causes:
The mains
experiences
instantaneous high-
voltage impact.
The output has
special loads such as
inductive loads and
rectication loads.
The output has
transformer loads
but the transformer
mode is not set.
The hardware is
damaged.
Measures:
After you rectify the
fault, restart the UPS.
Check whether the
load type is
supported by the
UPS.
Enable the
transformer mode.
Contact Huawei
technical support for
repair.
0040-05
Rectier
fault
Critical Manual
/Power-
o/
Automa
tic
The UPS shuts down.
The UPS transfers to another
working mode or shuts
down.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support for repair.
0040-06 Rectier
fault
Critical Power-
o
The UPS shuts down.
The UPS transfers to another
working mode or shuts
down.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support for repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 154