Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0061-01 Inverter
alarm
Minor Manual
/Power-
o/
Automa
tic
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
Parallel cables are
incorrectly
connected.
The lengths of
parallel cables vary
greatly.
Measures:
Reconnect cables.
The lengths of
parallel cables vary
within a range of
5%.
0061-02 Inverter
alarm
Minor Manual
/Power-
o
N/A Possible cause: The
EEPROM chip is faulty.
Measure: Contact
Huawei technical
support for repair.
0061-09 Inverter
alarm
Minor Automa
tic
The UPS may transfer to
another working mode or
shut down.
Possible causes:
There is a strong
interference source
onsite.
An internal fault
occurs in the UPS.
Measures:
Check and isolate the
strong interference
source onsite.
Contact Huawei
technical support.
0064-01 OL
timeout
Critical Automa
tic
The UPS automatically starts
after shutdown.
The UPS may transfer to
another working mode or
shut down.
Possible cause: The load
exceeds the rated
inverter loading
capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 164