EasyManuals Logo

Huawei UPS2000-G-10KRTL User Manual

Huawei UPS2000-G-10KRTL
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0084-03 Paral.
cable
alarm
Minor Replace the parallel
cable.
Contact Huawei
technical support for
repair.
0085-01 EPO Critical Manual
/Power-
o
The UPS shuts down. Possible cause: The EPO
button is pressed.
Measure: Restore the
EPO button status. Start
the UPS after the alarm
is cleared.
0086-01 BPS
trans.
overlimi
t
Minor Manual
/Power-
o/
Automa
tic
Transfer to an unstable side
is not allowed.
Possible cause: The
output transfer times
within 30 minutes
exceed the congured
value (3 by default).
Measure: Restart the
UPS after the alarm is
cleared.
0094-01 Redund
ancy
failure
Minor Automa
tic
N/A Possible causes:
The congured
number of redundant
UPSs exceeds the
maximum allowed
value.
The load exceeds the
rated loading
capacity of the
requisite UPSs in the
parallel system.
Measures:
Reduce the number
of redundant UPSs or
set the system to be
non-redundant.
Reduce the load or
replace the UPS with
a larger-capacity
UPS.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 167

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals