Page #71 background image
Figure 4-30 Bypass screen
Table 4-20 Bypass settings
Item Description Default
Value
Value Range
Max.
voltage
Upper threshold for the
bypass voltage. When
the dierence between
the bypass voltage and
the rated output voltage
exceeds this value, the
system determines that
the bypass voltage is
abnormal and that the
bypass is unavailable.
This parameter is
congurable only after
the inverter is shut
down.
15% 208 V: 10%, 15%,
20%, 25%, 30%
220 V (380 V in the
case of three-phase
output): 10%, 15%,
20%, 25%
230 V (400 V in the
case of three-phase
output): 10%, 15%,
20%
240 V (415 V in the
case of three-phase
output): 10%, 15%
Min.
voltage
Lower threshold for the
bypass voltage. When
the dierence between
the bypass voltage and
the rated output voltage
is greater than this
value, the system
determines that the
bypass voltage is
abnormal and that the
bypass is unavailable.
This parameter is
congurable only after
the inverter is shut
down.
20% 10%, 20%, 30%, 40%,
50%, 60%
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 63

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals