Precautions 
 
Before battery maintenance, get the tools, such as handles, insulated. Do not place metal 
tools on exposed battery terminals. 
 
Never use any organic solvent to clean batteries. 
 
Never try to remove the safety valve or fill anything into batteries. 
 
Never smoke or use fire around batteries. 
 
After battery discharge, charge batteries to ensure a required battery capacity. 
 
Only professionals are allowed to perform maintenance tasks. 
 
If batteries have not been discharged for a long time, discharge and charge them in 
equalized mode at least once every three months to activate them. Each charge should 
last at least 4 hours. 
 
Normally, discharge and charge batteries once every four to six months. Each charge 
should last at least 4 hours. 
 
In high-temperature areas, discharge and charge batteries once every two months. Each 
charge should last at least 4 hours. 
 
Do not overdischarge batteries. After discharging batteries, fully charge them within 24 
hours. 
 
Ensure that the battery discharge duration is 999 minutes at most and 0 minutes by 
default. If you set the value to 0 minutes, the discharge time is not limited. 
Routine maintenance items for batteries 
Table 7-2 Routine maintenance items for batteries 
No battery alarm is 
generated. 
Identify the cause 
based on the alarm 
information. 
1.  The surface is 
clean and tidy 
without stains. 
2.  The battery 
terminals are 
intact. 
3.  Batteries are free 
from damage and 
cracks. 
4.  Batteries are free 
from acid 
leakage. 
5.  Batteries are not 
deformed or 
bulged. 
If the battery 
appearance is 
abnormal, contact 
Huawei technical 
support. 
Battery operating 
temperature 
1.  The ambient 
battery 
temperature is 
25±5°C. 
1.  Identify the 
cause of the 
abnormal battery 
operating