EasyManua.ls Logo

Huawei UPS2000-G-2KRTL - ECO Feature

Huawei UPS2000-G-2KRTL
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Copyright © Huawei Technologies Co., Ltd.
77
Battery
Pack
Load
UPS2000-G-1KR
TL (min)
UPS2000-G-2KR
TL (min)
UPS2000-G-3KR
TL (min)
2 Battery
groups
100%
36.0
17.0
16.0
75%
47.0
25.0
25.0
50%
83.0
45.0
45.0
25%
159.0
85.0
85.0
3 Battery
groups
N/A
N/A
39.0
27.0
N/A
N/A
55.0
40.0
N/A
N/A
95.0
70.0
N/A
N/A
175.0
130.0
4 Battery
groups
N/A
N/A
63.0
39.0
N/A
N/A
87.0
55.0
N/A
N/A
147.0
95.0
N/A
N/A
267.0
175.0
The battery pack (ESS-36V12-9*2AHBPVBB01) for 1 kVA UPS with long backup time contain two
group battery strings. The battery pack (ESS-72V12-9AHBPVBB01) for 2 kVA UPS with long
backup time only contain one group battery strings. The battery pack (ESS-96V12-9AHBPVBB02)
for 3 kVA UPS with long backup time only contain one group battery strings.
The 1 kVA UPS with long backup time is allowed a maximum of two battery packs
(ESS-36V12-9*2AHBPVBB01) in parallel. The 2 kVA UPS with long backup time is allowed a
maximum of four battery packs (ESS-72V12-9AHBPVBB01) in parallel. The 3 kVA UPS with long
backup time is allowed a maximum of four battery packs (ESS-96V12-9AHBPVBB02) in parallel.
9.7 ECO Feature
Table 9-8 ECO feature
Item
1 kVA
2 kVA
3 kVA
ECO voltage
tolerance
Default value: ±22 V A (configurable on the LCD)
The range is ±(13 V AC-24 V AC)
ECO frequency
tolerance
±3 Hz