UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Copyright © Huawei Technologies Co., Ltd.
75
Item
1 kVA
2 kVA
3 kVA
mode (in line mode) after 10 minutes.
110%130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1 minutes.
130%150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 3 seconds.
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.
When the ambient temperature is 3540°C:
105%110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 5 minutes.
110%130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 30 seconds.
130%150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1.5 seconds.
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.
Dynamic voltage tolerance ±5%
±5%
Average frequency tracking rate
1 Hz/s
Transfer time
Transferring
from normal
mode to battery
mode
0
Bypass to ECO
or ECO to
bypass
4 ms (100% R Load)
Waveform (battery mode)
Sine wave
In frequency conversion mode, the output load is derated to 80% of the rated capacity.
If the output voltage is 200 V AC or 208 V AC, the output load is derated to 80% of the rated
capacity.