Alarm
ID
Alarm
Name
Severity Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
03
High
battery
voltage
Critical
The alarm is
automatically
cleared when
the battery
voltage is
lower than
58 V.
The battery
voltage is
greater than
60 V for 3s.
The system
shuts down
the inverter
and transfers
to bypass
mode.
Possible cause: The
battery is faulty.
Measure: Replace
the battery or
discharge the
battery to a normal
voltage.
Possible cause: The
sampling is faulty
due to
environmental
factors.
Measure: Send the
device to the
maintenance center.
04
Very
low
battery
voltage
Minor
The battery
voltage is
higher than
42 V and the
mains is
connected
properly.
The battery
voltage is
lower than
42 V.
The system
cannot supply
power in
battery mode.
If this alarm
is generated
in battery
mode, the
power output
will be
disconnected.
Possible cause: The
battery is faulty.
Measure: Replace
the battery or
charge the battery
to a normal voltage.
Possible cause: The
sampling is faulty
due to
environmental
factors.
Measure: Send the
device to the
maintenance center.
05
Output
short
-
circuit
Critical
The alarm
can be
automatically
cleared for
three times.
After that,
you need to
manually
clear the
alarm or
restart the
device.
The output
voltage is
lower than
50 V and the
current is
higher than
20 A for
more than
five cycles of
time.
The system
disconnects
the power
output.
Possible cause: The
load or cable is
short
-circuited.
Measure: Locate
and rectify the
short
-circuit fault.
06
High
output
voltage
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
voltage
exceeds the
rated
voltage by
20 V for 3s.
The system
shuts down
the inverter
and transfers
to bypass
mode.
Possible cause:
Load energy
backfeed
occurs.
Measure: Locate the
load and remove it.
Possible cause: The
circuit is faulty.
Measure: Send the
device to the
maintenance center.