12
Alarm Handling
6
Shutting Down the Inverter
5.3
1. Shut down loads.
2. Press and hold down OFF/ENTER for more than 5s. Release the button when you hear the
buzzer buzzing. The UPS shuts down the inverter and transfers to bypass mode. If mains
parameters are inconsistent with bypass parameters, the UPS transfers to standby mode.
3. Switch off the UPS AC input circuit breaker (on the power distribution cabinet or external
switch) and output circuit breaker (if any) based on site requirements.
4. Switch off the external battery circuit breaker (if any), or disconnect battery power cables (if
there is no external battery circuit breaker).