EasyManua.ls Logo

Huawei UPS2000-G-6KRTLL - Page 5

Huawei UPS2000-G-6KRTLL
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
1. The UPS2000-G-6KRTLL needs to connect to external lithium batteries ESM-48100B1 or
ESM-48150B1. Each UPS supports a maximum of 16 batteries connected in parallel. This
document uses four lithium batteries connected in parallel as an example.
2. When lithium batteries are connected, it is recommended that a DC circuit breaker (150 A 80
V DC circuit breaker for the 6 kVA UPS) be installed between the lithium batteries and the
UPS.
3. Before connecting cables to the UPS, ensure that the battery circuit breakers are OFF to
prevent operations with power applied.
4. If the UPS shares a battery string, the PE bar and battery busbar are configured.
Wiring Terminal Battery (BATT. 48VDC)
External Circuit Breaker 125 A (type D)
Cable Cross-sectional Area 25 mm²
Terminal Type OT-25 mm
2
-M8 terminal
Torque for Tightening Bolts 7 m
2. Install battery cables.
After lithium batteries are connected in parallel, connect signal cables to the BMS ports on
the UPS. Install a build-out resistor at the COM-OUT port on the last lithium battery.
Recommended power cable specifications
1UPS rear view 2Busbar
Installing battery cables (rack-mounted, front view)
All manuals and user guides at all-guides.com

Other manuals for Huawei UPS2000-G-6KRTLL

Related product manuals