EasyManua.ls Logo

Huawei UPS2000 - Page 11

Huawei UPS2000
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS2000-(6 kVA-20 kVA)
Modbus Protocol Development Guide
1 Communication Protocol
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Set toggle 4 to ON, as shown in Figure 1-3. This indicates that the Modbus protocol is
enabled. If both toggles 5 and 6 are set to ON, it indicates a two-wire system. If both of them
are set to OFF, it indicates a four-wire system.
Figure 1-3 Functional DIP switch S1
Table 1-2 Description of the functional DIP switch S1
Toggle Switch
Definition
Settings
Remarks
1
Reserved
ON: 0
OFF: 1
Toggle switches 1, 2, and 3 are
used together to set a 3-bit baud
rate.
Currently, the software version
supports only a baud rate of 9600
bits/s (in this case, toggle switches
1, 2, and 3 are ON).
2
Reserved
ON: 0
OFF: 1
3
Reserved
ON: 0
OFF: 1
4
RS485
protocol toggle
switch
ON: 0
OFF: 1
0: Modbus protocol
5
Toggle switch
for selecting a
two-wire or
four-wire
system
ON: two-wire
system
OFF: four-wire
system
Toggle switches 5 and 6 must be
both ON or both OFF.
6
Toggle switch
for selecting a
two-wire or
four-wire
system
7
Control area
network
(CAN)
build-out
resistor toggle
switch
ON: match
OFF: no match
None
8
RS485
build-out
ON: match
OFF: no match
None

Related product manuals