Add a schrader valve to the
smaller tube.
If it only drops a small amount
this does not mean that you
have an internal leak but that
the gas in the cabinet is cooler
and has reduced its pressure
because of this.
Attach the high side gauge of a
compound gauge to the valve
and pressurize the cabinet with
nitrogen or otherwise suitable
gas.
If the cabinet has an internal
leak contact the nearest
Hussmann distributor or the
factory to receive authorization
to return the cabinet to the
factory.
There should be at least 300 psi
on the system.
Mark the pressure on the gauge
and leave it, returning 24 hours
later.
NO CABINET WILL BE
ACCEPTED AT THE FACTORY
WITHOUT A LETTER OF
AUTHORIZATION FOR
RETURN.
Note the pressure. If it has
fallen more than 150-200 psi
then the system may have an
internal leak.
24