- 20 -
Parameter Meaning Range Default Remarks
0
To set the entering water temp.
under cooling mode
8-35℃ 28℃
Adjustable
1
To set the entering water temp.
under heating mode
15-40℃ 28℃
Adjustable
2
Entry into defrosting time period 30-90MIN 40MIN Adjustable
3
Terms of Entry defrosting function
-30℃to0℃ -7℃
Adjustable
4
Terms of Exit defrosting
2 to 30℃ 13℃
Adjustable
5
Time of Exit defrosting 1 to 12MIN 12MIN Adjustable
6
Mode: 0 Cool 1 Heat and Cool 2
Heat and cool+ auxiliary elec.
Heating 3 Heat
0-3 1(Heat and Cool) Adjustable
7
Mode selection of Electronic
expansion valve
0-1 1(auto) Adjustable
8
Superheat for heating target
-15℃-15℃ 3℃
Adjustable
9
Superheat for cooling target
-15℃-15℃ -2 ℃
Adjustable
A
Manual adjustment steps of
electronic expansion valve
18-94 70 Adjustable
B
Inlet water temperature
-9-99℃
Exact testing by value
C
Outlet water temperature
-9-99℃
Exact testing by value
D
Condenser temperature under
heating mode
-9-99℃
Exact testing by value
E
Gas return temperature
-9-99℃
Exact testing by value
F
Ambient temperature
-9-99℃
Exact testing by value
G
Condenser temperature under
Cooling mode
-9-99℃
Exact testing by value
H
Actual steps of electronic
expansion valve
N*5 Exact testing by value
L
Entering water temperature
calibration
-9.9-9.9℃ 0℃
Adjustable
Remarks:
(1) When HP stop running in 30 seconds, water pump will shut off automatically
(2) LED wire controller can operate the water pump after connected additional cable to the pump device in
the position of “PUMP” terminal accurately.
(3) It is necessary to put an extra 3-phase transfer device for 3 phase water pump.