Temporary
manual mode
at programme mode,press “ ”or“ ” to adjust
the value, it will automatic enter into temporary
manual mode
advanced options
advanced options can be classified to two sets
Hold down and at the same time for 3 seconds,it will display A1-A9,then press
to switch between these options
Displaying
symbol
Option
content
Press“ ”or“ ”to adjust value
temperature
compensatio
n(A1)
increment:0.5°C.
Start
differential
temperature
(A2)
Range:1°C~5°C:
1、When the setting temperature is higher than or equal to the sum of indoor
temperature and the start differential temperature, the heating equipment will turn on.
2、When the indoor temperature is higher than or equal to the sum of the setting
temperature and the start differential temperature, the heating equipment will turn off.
0 half locked:all keys are locked except for the on-off key;
1 full locked。all keys are locked including the on-off key。
Sensor
choice(A4)
N1:single build-in sensor;
N2:single build-out sensor;
N3:build-in and build-out sensor。
high
temperature
protection
(A5)
Range:35~70 When the lowest setting temperature is 35°C,press “ ”,it will display
“ ”, high temperature protection function is canceled; if the indoor temperature is
higher than the high temperature protection value,the heating equipment will be cut off.
Default value is =45°C
low
temperature
protection
(A6)
Range:5°C~10°C ;When the highest setting temperature is 10°C,press “ ”,it will
display “ ”, low temperature protection function is canceled; if the indoor
temperature is lower than the low temperature protection value,the heating equipment
will be cut off. Default value is =5°C
setting
temperature
lowest
limiting value
(A7)
Range:1°C~10°C: