EasyManua.ls Logo

IBC SFC-199 - Water Heater Installation Guidelines; Adjustable Temperature Setting

IBC SFC-199
7 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Combustion testing and adjustment
Danger
Acombustiontestchecksthatthegasvalveisoperatingproperlyinthefield.Toperformacombustiontest,you
mustbeaqualified,trainedandlicensedgasfitter.
Makingadjustmentstothegasvalvewithoutaproperlycalibratedgascombustionanalyzerandbypeoplewho
arenottrainedandexperiencedinitsuseisforbidden.Failuretouseananalyzercanresultinanimmediate
hazard.
Model Number High Fire Input
SFC-199
125MBH(onaheavyload,only
DHWprovidesfullinputof199
BTUs)
Table 3 - Rated input of a converted appliance
Normalignitionsystemsequenceofoperation:
Theappliance'scontrol,uponacallforDHW,turnsonthecombustionfanforashortpre-purge,thenenergizesthespark
electrodeandgasvalvefora5-secondtrialforignition.
Iftheburnerdoesnotlight,theprocessisrepeateduntiltheburnerlightsandflameisdetected.After4unsuccessfultrials
forignition,theappliancelocksoutandwillneedtobemanuallyresetbypressingtheReturnArrow button.
To perform a combustion test and adjustment:
1. Turnofftheappliance’sgasshut-offvalve.
2. Withasmallflatscrewdriver(1/8"or3mm),opentheinletgassupplypressuretest
portbyturningitsscrew1fullturncounterclockwise.
3. Attachamanometertotheinletpressuretestportandturnongastoappliance.
Staticmanometerreadingshouldbeideally11"w.c.forpropane.
Minimumandmaximumstaticpressuremustbebetween5"and14"w.c.
Monitorpressurethroughoutthecommissioning(start-up)procedure.
Pressuremaydroopupto1"w.c.athighfire.
4. Tosettheappliancetohighfiremanually,createalargedemandbyturningupallthethermostatsorcreatealarge
DHWdemandfortheappliancetoheat.
Note:AllowtheappliancetooperateatHighFirefor3minutestostabilize.(Theapplianceoperatesinmanual
modefor10minutesthenswitchbacktothenormaloperatingmode.Toextendmanualmodeoperation,pressthe
Service andPlusbuttonstogethertwicewhiletheapplianceisoperatinginmanualmodetoresetthetimerfor10
4 |

Other manuals for IBC SFC-199