Clocking the Meter (for Natural Gas only)
1. Turnoffallotherappliancesandpilots.
2. Turnontheapplianceandsettheappliancetohighfire.
3. Ensuretheappliancehasalargeloadtoheat,sothattheappliancewillnotshutoff.
4. WithaStop-Watch,recordthenumberofsecondsforthesmallestdialtomake1fullrevolution.
5. CFH=(3600xDialSize)/Seconds.
6. CFHx1000(checklocalBtucontent)=InputBtu’s.
Note
For2PSImetersmultiplyCFHx1.097
ForMetricmetersmultiplyCFHx35.3
For2PSImetricmetersmultiplyCFHx1.097x35.3
ForAltitudeabove4,500'deduct2%per1,000’ofaltitudefromtheInputBtu’s.