SFC-199 - Fuel Conversion to Propane (NG to LP) Kit P-844
| 5
moreminutes.)Donotmakeadjustmentsiftheservicedisplayshowsan“h”,indicatingthattheappliancehas
reducedoutputbecauseitisbecomingtoohot.
5. Clockthegasmeter(seeinstructionsClocking the Meter (for Natural Gas only) on page 6)toconfirmfull
maximumratingplateinput.
a. Withacombustionanalyzerprobeinthefluegastestport,checkthemeasuredresultsagainstTable 1 -
HighFire.
b. Iftheresultsareoutsidethepermittedrange,checktheinletpressure,andconfirmthatthecorrectorifice
andventuriareinstalled.
6. SwitchtheappliancetolowfirebypressingtheServicebuttonandMinusbuttonsatthesametime.The
appliancewilldroptolowfire.“L”willshowintheservicedisplay.
a. ComparethereadingswithTable 1 -LowFire.Ifadjustmentisnecessary,removetheLowFire
AdjustmentcaptorevealaTorxheadscrew.
b. Maketinyadjustments,typicallylessthan1/8thofaturnatatime.Turnthescrewclockwisetoincrease
CO
2
andcounter-clockwisetoreduceCO
2
.Ifthetargetcannotbemet,evenafterahalfturn,contactthe
factory.
c. Whenfinished,replacetheLowFirecap,andleavethemanualmodebypressing+AND-
simultaneously.
7. Switchofftheappliancebypressingthespaceabovethewhitedot.
8. Turnoffthegasattheappliance'sgasshut-offvalve.
9. Removethefluegasanalyzerfromthetestport,andreinstallthetestportcap.
10. Removethegaspressuremanometerfromthegasvalve,andclosethetestport.
11. Turnonthegasattheappliance’sgasshut-offvalve.
12. Ensuretherearenogasleaksbeforereinstallingthefrontcover.
13. Turnontheappliancebypressingthespaceabovethewhitedot.