Clocking the Meter (Natural Gas)
1. Turnoffallotherappliancesandpilots.
2. Turnontheboilerandsettheboilertohighfire.
3. Ensuretheboilerhasalargeloadtoheat,sothattheboilerwillnotshutoff.
4. WithaStop-Watch,recordthenumberofsecondsforthesmallestdialtomake1fullrevolution.
5. CFH=(3600xDialSize)/Seconds.
6. CFHx1000(checklocalBtucontent)=InputBtu’s.