EasyManua.ls Logo

IBC SL SERIES - Specifications

IBC SL SERIES
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Specifications
Boiler Specification SL 26-260 G3 SL 40-399 G3
CSA Input (Natural Gas or Propane)
26 - 260 MBH
40 - 399 MBH
CSA Input (Natural Gas or Propane) 7.6 - 76.2 kW
11.7 - 117 kW
CSA Output 24.9 - 239 MBH
38.4 - 383 MBH
CSA Output
7.31 - 70.0 kW 11.2 - 112 kW
A.F.U.E 95% -
Combustion Efficiency - 96%
Thermal Efficiency (ANSI/AHRI-1500) - 96%
Minimum gas supply pressure (Natural Gas or Propane) 4" w.c. 4" w.c.
Maximum gas supply pressure (Natural Gas or Propane) 14" w.c. 14" w.c.
Minimum Ambient temperature 32°F / 0°C 32°F / 0°C
Maximum Ambient temperature 122°F / 50°C 122°F / 50°C
Max. relative humidity (non-condensing) 90% 90%
Minimum water temp. 34°F / 1°C 34°F / 1°C
Maximum water temp. (electronic hi-limit) 190°F / 88°C 190°F / 88°C
Max. ΔT - supply/return (electronic fence) 40°F 40°F
Max. Water Temperature Lockout Limit 201°F / 94°C 201°F / 94°C
Power use (120Vac/60Hz) @ full fire (less pumps) 127 W 190 W
Weight (empty) 162 lbs / 74 Kg 240 lbs /110 Kg
Heating Surface Area 22.71 ft
2
/ 2.11 m
2
36.56 ft
2
/ 3.40 m
2
Pressure vessel water content 4.64 USG/ 17.6 L 6.66 USG/ 25.2 L
Maximum boiler flow rate 25 USgpm 45 USgpm
Minimum boiler flow rate 6 USgpm 20 USgpm
Maximum operating water pressure* 30 psig/ 206 kPa 80psig/ 551 kPa
Minimum water pressure 8 psig / 55 kPa 8 psig / 55 kPa
Approved installation altitude - ASL 0 - 12,000’ 0 - 12,000’
Maximum equivalent vent length , each side (vent & air
intake) - Natural gas or propane. Air intake options:
either direct vent or indoor supply
200’ (3") 200’ (4")
* Boilers are shipped with a 30 psig pressure relief valve.