BOILER SYSTEMS AND OPERATION
VFC 15-150 - VFC 45-225 MODULATING GAS BOILERS
2.6.4 Variable Speed Pumping
This section reserved.
2.6.5 Temperature Setback
For heating loads declared as Space Heating (e.g. with Outdoor Reset) and/
or DHW (where a thermistor probe is used), there are provisions for entering
temperature setback intervals. During the setback period, the boiler supply
watertemperaturetargetisadjustedfromthepre-setxedoroating(with
Outdoor Reset) levels. There is a simultaneous movement in the Indoor Setpoint
Temperature or DHW Tank Setpoint, to yield a consistent spread and avoid
undesirable cycling. Normally users would apply this feature to achieve fuel
savings during night-or-away hours. It is also possible to use the feature to
set forward (up) the temperature; this may be of use for certain commercial
applications where short-term high temperature DHW service is desired.
Up to 56 events / week can be programmed for each eligible load – for example,
DHW can be set back twice and returned (twice) each day. The routine can be
appliedbyspecicday(Mon-Sun).
The automated setback feature cannot be applied to setpoint loads, including
DHW with simple aquastat control. This is due to the lack of linkage with the
thermostat; setback without linkage could lead to unacceptable cycling.
Access is via the User Setup screen.
2.6.6 Unoccupied Mode
Users can further reduce energy consumption by switching the boiler to the
unoccupied mode during holidays or other away periods.
While in the Unoccupied mode, the DHW load is turned off, while Space Heating
loads for which Outdoor Reset is activated will drop both the circulating water and
the indoor setpoint temperature parameters to 50°F. Set Point controlled loads
are not adjusted through this process, to avoid the potential for boiler cycling as
there is no linkage with the relevant thermostat.
On the main User Setup Menu, select “Occupancy Status”, then toggle between
Occupied (top button) and Unoccupied (lower button) as desired.
2.6.7 Summer Shutdown
During the Installer set up process, a cut-off level for outdoor temperature can be
selected - to curtail any further space heating. This is typically used to turn off an