30
1.4 POWER UP
At the first power up, the display shows --- which means no parameter has been pro-
grammed yet.
Under these conditions, a manual test of the steps can be conducted to check the con-
nections.
Press the + or – key to connect or disconnect the steps.
WARNING! During this phase, the step control is totally manual and the unit does not
control the reconnection time to allow the capacitors to discharge.
1.5 PARAMETER SET-UP
There are various methods of setting parameters and commissioning the controller to op-
erate properly, namely:
− Section 1.6 MANUAL KEYPAD SET-UP
− Section 1.9 QUICK SET-UP VIA PC
− Section 1.11 AUTOMATIC SET-UP
1.6 MANUAL KEYPAD SET-UP
5 sec
− Place the unit in manual mode and press the
MODE key for 5 consecutive seconds.
− The wording SEt appears on the display to con-
firm access to the basic menu parameters.
previous
parameter
next
parameter
− Press the MANU/AUTO key to enter the next
parameter.
− Press the MODE key to return to the previous
parameter.
− Press the + and - keys to view and change
the setting of the selected parameter. If no
key is pressed for a few seconds, the se-
lected parameter is displayed once again.
− Exit from set-up is automatic once the last
parameter is exceeded.
display and modify
parameter