PC and the relative software (order code A25060000000045), used for the quick parame-
ter set-up.
The following table indicates the alarm codes and the relative meaning of each along with
the default setting.
ALARM
CODE
DESCRIPTION
A01 Under compensation
15min
A02 Over compensation
120s
A03 Low current
5s
A04 High current
60s
A05 Low voltage
5s
A06 High voltage
15min
A07 Capacitor overload
180s
A08 Overtemperature
5min
A09 No-voltage release
0s
Note:
None of the above-indicated alarms are non-volatile.
In MANU mode the steps disconnection takes place only for the No voltage release
(micro-breaking) alarm A09 - No-voltage release.
A01 - Under compensation
Capacitors are all connected and cosf is lower than the set-point value.
A02 - Over compensation
All capacitors are disconnected and cosf is higher than the set-point value.
A03 - Low current
Current value is lower than 2.5% full scale value. In automatic, the capacitors are discon-
nected after 2 minutes of the alarm activation.
A04 - High current
Current value is 120% higher than full scale value.
A05 -Low voltage
Voltage value is -15% lower than lower rated voltage.
A06 - High voltage
Voltage value is +10% higher than higher rated voltage.
A07 - Capacitor overload
Current value flowing in the capacitors is higher than the set threshold (refer to P.20 and
P.21 of advanced menu).