4
Preservation Instructions
Unpacking Inspection
Caution: It is recommended using gloves and protective eyewear when unpacking
Verify product is as identified on the packing list. Air conditioner should arrive banded to pallet in the proper
upright position. See arrows on packaging for verification. Any evidence of damage should be noted on the freight
bill. The freight carriers claim procedure should be followed. Ice Qube cannot accept responsibility for damages
that occur during shipping. If the shipping container was damaged or marred in any way, check for scratches,
dents, loose hardware, presence of oil or any other irregularities with the Ice Qube TMS.
Package Contents
Included in the shipment with the air conditioner will be:
1. Operation manual
2. Mounting hardware
3. Condenser air diverter plate
4. Standard master warranty
5. Ethernet controller manual (Optional)
6. Enclosure gasket (Pre-installed)
Handling
Ice Qube recommends that the unit remains in the proper upright position, as indicated on the shipping container.
The unit must remain upright for a minimum of 24 hours before initial operation to ensure oil has returned to the
compressor. Operation before the 24-hour time may cause compressor damage and shorten the life of the system.
Operation before this 24-hour period will void all warranties.
Storage
The storage space temperature should be in the range of -40 to 85°C (-40 to 185°F) in a non-condensing
environment.
HAZARDOUS LOCATIONS MODELS ONLY - CONDITIONS OF ACCEPTABILITY:
When installed in the end use equipment, the following considerations are to be examined:
1. The maximum operating temperature of the devices while subjected to the temperature test at a 60°C
ambient air temperature is in accordance with the temperature class of the below table:
Maximum Temperature
T-Code
Unit
120°C
T4A
IQ1-2-3-4-5-6-8-10-12000EV
160°C
T3C
IQ14-17-20000EV
2. The subject devices must be used within their Recognized “Ratings” and conditions of acceptability as
referenced in the User’s Manual.
3. Consideration is to be given to the Conditions of Acceptability specified in the individual recognitions
when these components are employed in the end-use equipment.