12
9. Status Indicator Light (Lt 0 or 1)
0 = Status indicator never on
1 = Status indicator on with first stage
Press the or button to select.
Note: Red light indicates heating cycle and green light indicates cooling cycle
Slide the Mode switch to Heat or Cool to exit configuration.
8. Filter Check time (300-800, – – –)
Set Fan Run Time (in hours) when Check Filter is displayed or set to – – – to disable.
Press the or button to select.
Note: To reset filter counter to zero and clear filter warning, press the and
buttons simultaneously for 5 seconds.
Press the
SW6 button
to advance to the next screen.
7. Maximum heating or cooling cycles allowed per hour (-, 2-6)
- = as many as needed, 2-6 = maximum cycles/hour
Press the or button to select.
Press the
SW6 button
to advance to the next screen.
FILTER
SET
ROOM
SET
SET
SET
6. Room temperature offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note: When not set to 0, ROOM will display
Press the or button to select.
Press the
SW6 button
to advance to the next screen.