Situation #5: An incorrect ID of the Modbus slave device is being specified.
Solution: Check and fix the difference of ID number between the polling definition and the
slave device.
Situation #6: The Timeout or PollDelay setting is not long enough.
Solution: Lengthen the Timeout or PollDelay setting until it is suitable for communication with the
slave device.