What to do if I cannot communicate via Ethernet port with ICP DAS USA Control Unit?
- CCarol MunozAug 7, 2025
If you cannot communicate via the Ethernet port on your ICP DAS USA Control Unit, but the ET-7000 is still operating, there might be a few reasons: * The IP/Mask/Gateway address isn’t within the IP address range of the LAN. To solve this, change the IP/Mask/Gateway address to match the LAN, or ask the MIS administrator for assistance. * The IP address has restricted by the IP filter settings. Check the IP filter setting using the Web configuration. * There are more than 30 TCP/IP connections. Reboot the module.