7. FAQ
Q1: What are the maximum numbers of polling definition and local register?
A1: The maximum number of polling definition in a MDC-700 is 250, each definition can access up to
125 registers. Each of the four tables (DI/DO/AI/DO) can store up to 9600 registers for polled data.
Q2: What is the maximum number of registers can be accessed in one Modbus
command?
A2: By following the Modbus protocol, the maximum amount of registers that one command can
access is 255 of function code 01 and 02, and 126 of function code 03 and 04.