4. Configuration
The necessary configuration for Modbus TCP/Modbus RTU communication and polling definition is
handled by a single file named config.csv. Just follow the easy-to-use format defined in the
config.csv file to edit the configuration parameters and import the new file via a simple mouse-click,
the data on connected Modbus RTU slave devices can be accessed via Ethernet.
Only the Function code 01/02/03/04 can be used in the config.csv file:
01: Read Coil Status (Read DO)
02: Read Input Status (Read DI)
03: Read Holding Registers (Read AO)
04: Read Input Registers (Read AI)
If you would like to write data to a digital or analog output channel on a Modbus RTU slave device,
the output channel needs be mapped with a local register address in the MDC-700 by editing the
polling definition with using corresponding read function code (01 or 03). Refer to section 6. FAQ-Q4
for more detailed steps.
The following section intends to guide you to set up your MDC-700 module. After completing the
following steps, you can obtain configuration and other information related to the MDC module and
associated slave devices in your browser.
Basic operating procedure
Step 1: Export the config.csv file from MDC-700.
Step 2: Edit the config.csv file.
Note that before editing this file, you should confirm the parameter value for all associated
slave devices.
Step 3: Import the config.csv file to the MDC-700.