EasyManua.ls Logo

ICP F9MVE0401410A - Sequence of Operation

ICP F9MVE0401410A
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace: (F/G)9MVE
Specifications subject to change without notice.
440 04 4800 00 30
Sequence of Operation
NOTE: Furnace control must be grounded for proper operation
or else control will lock out. Control is grounded through
green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram in Figure 16, follow the sequence
of operation through the different modes. Read and follow the
wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1andW2), the control will start a 90second
bloweronly ON period two seconds after power is restored, if
the thermostat is still calling for gas heating. The amber LED
light will flash code 1+2 during the 90second period, after
which the LED will flash a heartbeat (brightdim), as long as no
faults are detected. After the 90second period, the furnace will
respond to the thermostat normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hotsurface igniter HSI, and gas valve GV.
1. TwoStage Heating (Adaptive Mode) with
SingleStage Thermostat
NOTE: The lowheat only switch SW12 selects either the
lowheat only operation mode when ON, (see item 2. below) or
the adaptive heating mode when OFF in response to a call for
heat. (See Figure 5) When the W2 thermostat terminal is
energized it will always cause highheat operation when the
RtoW circuit is closed, regardless of the setting of the
lowheat only switch. This furnace can operate as a twostage
furnace with a singlestage thermostat because the furnace
control CPU includes a programmed adaptive sequence of
controlled operation, which selects lowheat or highheat
operation. This selection is based upon the stored history of the
length of previous gasheating periods of the singlestage
thermostat.
The furnace will start up in either low or highheat. If the
furnace starts up in lowheat, the control CPU determines the
lowheat ontime (from 0 to 16 minutes) which is permitted
before switching to highheat.
If the power is interrupted, the stored history is erased and the
control CPU will select low
heat for up to 16 minutes and then
switch to highheat, as long as the thermostat continues to call
for heat. Subsequent selection is based on stored history of the
thermostat cycle times.
The wall thermostat “calls for heat”, closing the RtoW circuit.
The furnace control performs a selfcheck, verifies the
lowheat and highheat pressure switch contacts LPS and
HPS are open, and starts the inducer motor IDM in
highspeed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects lowheat
operation the inducer motor IDM comes up to
speed, the lowheat pressure switch LPS closes,
and the furnace control CPU begins a
15second prepurge period. If the lowheat
pressure switch LPS fails to remain closed the
inducer motor IDM will remain running at
highspeed. After the lowheat pressure switch
recloses the furnace control CPU will begin a
15second prepurge period, and continue to run
the inducer motor IDM at highspeed.
(2.) If the furnace control CPU selects highheat
operation, the inducer motor IDM remains
running at highspeed, and the highheat
pressure switch relay HPSR is deenergized to
close the NC contact. When sufficient pressure is
available the highheat pressure switch HPS
closes, and the highheat gas valve solenoid
GVHI is energized. The furnace control CPU
begins a 15second prepurge period after the
lowheat pressure switch LPS closes. If the
highheat pressure switch HPS fails to close and
the lowheat pressure switch LPS closes, the
furnace will operate at lowheat gas flow rate
until the highheat pressure switch closes for a
maximum of 2 minutes after ignition.
b. Igniter WarmUp At the end of the prepurge period,
the HotSurface Igniter HSI is energized for a
17
second igniter warmup period.
c. TrialForIgnition Sequence When the igniter
warmup period is completed the main gas valve
relay contact GVR closes to energize the gas valve
solenoid GVM. The gas valve solenoid GVM
permits gas flow to the burners where it is ignited by
the HSI. Five seconds after the GVR closes, a
2second flame proving period begins. The HSI
igniter will remain energized until the flame is sensed
or until the 2second flame proving period begins. If
the furnace control CPU selects highheat operation,
the highheat gas valve solenoid GVHI is also
energized.
d. FlameProving When the burner flame is proved
at the flameproving sensor electrode FSE, the
inducer motor IDM switches to lowspeed unless the
furnace is operating in highheat, and the furnace
control CPU begins the blowerON delay period and
continues to hold the gas valve GVM open. If the
burner flame is not proved within two seconds, the
control CPU will close the gas valve GVM, and the
control CPU will repeat the ignition sequence for up
to three more TrialsForIgnition before going to
IgnitionLockout. Lockout will be reset automatically
after three hours, or by momentarily interrupting 115
vac power to the furnace, or by interrupting 24 vac
power at SEC1 or SEC2 to the furnace control CPU
(not at W/W1, G, R, etc.). If flame is proved when
flame should not be present, the furnace control CPU
will lock out of GasHeating mode and operate the
inducer motor IDM on high speed until flame is no
longer proved.
e. BlowerOn delay If the burner flame is proven the
blowerON delays for lowheat and highheat are as
follows:
Lowheat 45 seconds after the gas valve GVM is
opened the blower motor BLWM is turned ON at
lowheat airflow.
Highheat
25 seconds after the gas valve GVM is
opened the BLWM is turned ON at highheat airflow.
Simultaneously, the humidifier terminal HUM and
electronic air cleaner terminal EAC1 are energized
and remain energized throughout the heating cycle.
f. Switching from Low to HighHeat If the furnace
control CPU switches from lowheat to highheat, the
furnace control CPU will switch the inducer motor
IDM speed from low to high. The highheat pressure
switch relay HPSR is deenergized to close the NC
contact. When sufficient pressure is available the
highheat pressure switch HPS closes, and the
highheat gas valve solenoid GVHI is energized.
The blower motor BLWM will transition to highheat
airflow five seconds after the furnace control CPU
switches from lowheat to highheat.
g. Switching from High to LowHeat The furnace
control CPU will not switch from highheat to
lowheat while the thermostat RtoW circuit is
closed when using a singlestage thermostat.
h. BlowerOff Delay When the thermostat is satisfied,
the R to W circuit is opened, deenergizing the gas

Related product manuals