Under-Voltage Recovery: Set the voltage that will clear the alarm on
this bus. Bus voltage rising above this level will clear the alarm. The
default setting is 12 VDC.
Activate Alarm Form C Contact: Set the check box for the Alarm relay
to trigger for an undervoltage condition. The default setting is Disabled.
Send E-mail: Set the check box to have a Bus Under-Voltage alarm e-
mail sent to the e-mail addresses set up on the "E-mail Setup" page (see
Section 4.8). The default setting is Disabled.
Bus "A/B" Over-Voltage Alarm
Over-Voltage Threshold: Set the voltage that will trigger an overvoltage
alarm on this bus. Bus voltage rising above this level will immediately
trigger a Bus Over Voltage alarm. Bus voltage under this threshold for
will clear the alarm. The default setting is 60 VDC.
Activate Alarm Form C Contact: Set the check box for the Alarm relay
to trigger for an overvoltage condition. The default setting is Disabled.
Send E-mail: Set the check box to have a Bus Over-Voltage alarm e-
mail sent to the e-mail addresses set up on the "E-mail Setup" page (see
Section 4.8). The default setting is Disabled.
Bus "A/B" Over-Current Alarm
Over-Current Threshold: Set the current that will trigger an overcurrent
alarm on this bus. Bus current above this level for at least 5 seconds will
trigger the Over-Current Alarm. The default setting is 100 amps.
Activate Alarm Form C Contact: Set the check box for the Alarm relay
to trigger for an overcurrent condition. The default setting is Disabled.