Power-On Sequencing/Cycling
Sequence/Cycle Delay: Set the time in seconds (0–60 seconds) that
will be used as the delay between energizing outputs. Will affect all
outputs. Set to 0 to disable. Use this feature to allow a delay between
energizing loads to reduce inrush current. The default setting is 0
(Disabled).
The "Sequence Delay" time will also be used as the "Power Cycling" time
delay for each output that has the "Power Cycling" feature enabled on
the "Output Setup" page (see Section 4.6).
Reverse Sequence Order: Select the check box to cause the power-on
sequence to run in reverse order with output 6 on first, ending with output
1, when the "Enable Bus" button is clicked on the Status & Control page.