EasyManua.ls Logo

IDEC FC4A-C10R2 - Troubleshooting Diagram 7

IDEC FC4A-C10R2
525 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29: TROUBLESHOOTING
29-14 « FC4A MICROSMART USERS MANUAL »
Troubleshooting Diagram 7
Does the monitored
input turn on and off?
NO
YES
NO
YES
YES
Call IDEC for assistance.
Monitor the designated stop or
reset input using WindLDR on a
computer.
NO
Is the designated stop or
reset input on?
Is M8000 off?
Turn on the designated input.
The input circuit in the CPU mod-
ule is damaged.
Replace the CPU module.
Is stop or
reset input designated in
the WindLDR Function Area
Settings?
Monitor the start control special
internal relay M8000 using
WindLDR on a computer.
YES
Turn off the star t control special
internal relay M8000 using
WindLDR on a computer.
NO
Cannot stop or reset operation.
Note: To monitor M8000, from the WindLDR menu bar,
select O
nline > Monitor, then Online > Direct Monitor.
Enter M8000 in the Direct Monitor Dialog.
Note: To turn off M8000, from the WindLDR menu bar, select
O
nline > Monitor, then Online > Direct Set/Reset. Enter
M8000 in the Direct Set/Reset Dialog. Click Reset.