26
DEADBAND OPERATION - Controls one Heat and one Cool stage with
a three speed fan (see below).
The low speed fan for heat or cool is turned on when: The temperature
spread from the setpoint is equal to or greater than: the setpoint plus the
1st stage deadband (Setup Step 11, page 17). This 1st stage deadband
is adjustable from 1-6 degrees and the default is two degrees.
The medium speed fan for heat or cool is turned on when: The
temperature spread from the setpoint is equal to or greater than: the
setpoint plus the 1st stage deadband (Setup Step 11, page 17), plus the
2nd stage dead-band. This 2nd stage deadband is xed at one degree
and is not adjustable.
The high speed fan for heat or cool is turned on when: The temperature
spread from the setpoint is equal to or greater than: the setpoint plus
the 1st stage deadband (Setup Step 11, page 17), plus the 2nd stage
deadband, plus the 3rd stage deadband. This 3rd stage deadband is
xed at one degree and is not adjustable.
TEMPERATURE
DECREAS
EI
NCREASE
Cool
SP
Heat
SP
Med-
speed
fan
W1
Med-
speed
fan
Y1+Y2
Heating
Cooling
Lo-
speed
fan
W1
Hi-
speed
fan
W1
Lo-
speed
fan
Y1
Hi-
speed
fan
Y1+Y2
DB3
DB2
DB1
-6˚1˚-
DB1DB2 DB3
About Advanced Features & Operation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IEC E055-71520330 and is the answer not in the manual?

IEC E055-71520330 Specifications

General IconGeneral
BrandIEC
ModelE055-71520330
CategoryThermostat
LanguageEnglish

Related product manuals