Table 3 Table of easy compact parameters for CURP, CURLP and CURHP
Par.
Description
Def.
UOM.
Min
Max
St
set point
2
°C
r1
r2
PS
password
22
-
0
99
/2
probe measurement stability
4
-
1
15
/4
select probe displayed
1
-
1
3
/5
select °C/°F
0
-
0(°C)
1(°F)
/6
disable decimal point
0
-
0
1
/C1
probe 1 offset
0.0
°C
-50.0
50.0
/C2
probe 2 offset
0.0
°C
-50.0
50.0
/C3
probe 3 offset
0.0
°C
-50.0
50.0
rd
control differential
3.0
°C
0
19.0
r1
minimum set point value
0.0
°C
-50.0
r2
r2
maximum set point value
15.0
°C
r1
99
r3
select direct/reverse operation
0
-
0
2
r4
night-time set point delta
3.0
°C
-50
50
c0
compressor and fan start delay on power-up
1
min
0
100
c1
minimum time between consecutive compressor starts
3
min
0
100
c2
minimum compressor off time
0
min
0
100
c3
minimum compressor on time
2
min
0
100
c4
compressor on time with duty setting
50
min
0
100
cc
continuous cycle duration
2
2
0
15
c6
temperature alarm bypass after continuous cycle
2
h
0
15
d0
type of defrost
0
-
0
4
dI
interval between defrosts
6
h
0
199
dt
end defrost temperature set point
12.0
°C
-50
130
dP
maximum defrost duration
30
min
1
199
d4
defrost when switching the instrument on
0
-
0
1
d5
defrost delay on power-up or when enabled by digital input
0
min
0
199
d6
freeze control temperature display during defrost
1
-
0
1
dd
dripping time
2
min
0
15
d8
alarm bypass time after defrost
2
h
0
15
d9
defrost priority over compressor protectors
0
-
0
1
d/
defrost probe reading (2)
-
°C
-
-
dC
time base
0
-
0
1
A0
alarm and fan temperature differential
2.0
°C
-20
+20
AL
absolute/relative temperature for low temperature alarm
0.0
°C
-50
+99
AH
absolute/relative temperature for high temperature alarm
0.0
°C
-50
+99
Ad
temperature alarm delay
0
min
0
199
A4
3rd input configuration
0
-
0
11
A7
digital input alarm delay
0
min
0
199
A8
enable alarm “Ed” (end defrost by timeout)
0
-
0
1
AC
set point dirty condenser alarm
60
°C
-50
250
AE
dirty condenser alarm differential temperature
3.0
°C
0.1
20
Acd
dirty condenser alarm delay
0
min
0
250
F0
enable evaporator fan control
0
-
0
1
F1
evaporator fan control set point
5.0
°C
-50
130
F2
stop evaporator fan if compressor off
0
-
0
1
F3
evaporator fan status during defrost
0
-
0
1
Fd
post-dripping time
2.0
min
0
15
H0
serial address
1
-
0
207
H1
AUX output configuration
0
-
0
2
H2
enable keypad
1
-
0
2
H4
disable buzzer
0
0
1