User manual Elba www.igloo.pl
6. SERVICE
6.1. Fault identi cation and repair
In case of any dif culties during actuation of the device or during its exploitation, please return to these chapters in this ma-
nual, which explain the performed operation. This aims to ensure that the device is properly operated. If you still experience
dif culties, the following hints will help you solve the problem.
The device is not working... – Make sure that:
The device is connected to the supply network
Voltage and frequency in the network are compliant with those recommended by the producer 230V/50Hz
The main switch is turned on
Thermostat is switched on (Concerns the Igloo thermostat – If only two dots are displayed on the screen – turn on the thermo-
stat)
The device is operating, the lighting is switched off... – Make sure that:
The lighting switch is on
Fluorescent lamp or the starter of the device are not burnt
The device does not reach the proper temperature, the lighting is on...– Make sure that:
The main switch is on
Temperature setting on the thermostat is properly set
The thermostat is operating properly
Make sure that the condenser is not lthy, and clean the condenser when necessary
Ambient temperature does not exceed 25ºC
Enough time has passed for products to be cooled
Too much fresh food has been placed in the cabinet and the maximum freezing capability has not been exceeded
Door of the devices close properly and whether the seal adheres to the body of the device
Ventilation holes of the device are not blocked
(This concerns the “IGLOO” thermostat) thermostat displays C0 or C1 or C2 instead of displaying temperature:
This situation shall occur, when one of temperature regulation sensors has been destroyed. The following messages
may be displayed in such case:
C0 – temperature sensors inside the chamber are damaged – call authorized service
C1 – failure of evaporator sensor - call authorized service
C2 – failure of condenser alarm sensors (or failure of second evaporator sensor) – call authorized service
(This concerns the “IGLOO” thermostat) The device is working, sound signalling is activated...– Make sure that:
The condenser is clean, if necessary – clean the condenser
Condenser ventilator is working properly
Ambient temperature does not exceed 25ºC
The device is working too loud...– Make sure that:
The device is standing stably and is properly levelled
Furniture adjoining the device do not vibrate when the compressor is working
Internal elements have been properly mounted
Steam precipitation on glasses of the device is a normal phenomenon in case of high relative air
humidity exceeding 60% and does not require calling the service!
Noises made by the operating device are a normal phenomenon. The devices are equipped with venti-
lators, engines and compressors, which turn on and off automatically Each compressor makes certain
noises when operating. These sounds are made by the aggregate engine and by cooling agent
owing through the circuit. This phenomenon constitutes a technical feature of cooling devices
and it does not signify their faulty work.
Elements of device can corrode when improper used and maintenance. To avoid that please
follow the rules:
• Do not allow contact of the surface of the device with substances containing chlorine and / or baking
soda in different varieties, which destroy the protective layer and components of the device (also
includes various stainless steel)