SCA0410S - Single Pole
SCA0410N - Neutral Disconnect
SCA0410D - Double Pole
SCA1210S - Single Pole
SCA1210N - Neutral Disconnect
SCA1210D - Double Pole
Common specifications as detailed on
page 12 plus the following:
Key Features
SCA0410
l - 4 x 10 Amp fully rated Source Controller.
SCA1210
l - 12 x 10 Amp fully rated Source Controller.
l Auto Senses for load type, and suitable for resistive,
inductive and capacitive loads.
l Complete with iPROTECT™ lamp protection and auto
short circuit protection.
Mechanical Data
SCA0410
l Weight: 9kg.
l Mains Cable Access: 4 x 25 mm, 4 x PG16 and
1 x PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCA1210
l Weight: 18kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
Electrical Data
SCA0410
l Maximum Load: 40 Amp single phase @ 40ºC.
l Maximum Channel Current: 10 Amps.
l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 10 Amp MCB’s type C, 6KA rated.
SCA1210
l Maximum Load: 40 Amp three phase @ 40ºC.
l Maximum Channel Current: 10 Amps.
l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 10 Amp MCB’s type C, 6KA rated.
Load Types
l Incandescent 230 volt lamps.
l Low voltage inductive lamps (wire wound or
electronic).
l Low voltage electronic (capacitive).
l Cold Cathode (Check the iLight™ help desk for
details).
Minimum Load
l 20 watts per channel.
Dimmed Outputs
l 2 x 45 Amp FET’s per circuit.
Switched Outputs
l The Dimmed outputs may be configured as switches,
for non-dimmed loads. They require a minimum load
of 30mA for them to latch.
Terminal Sizes
SCA0410, SCA1210
l Incoming supply, maximum cable size: 10mm
2
.
Adaptive Source Controllers
19 of 23
INTELLIGENT CONTROLS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the iLight SCI0405 and is the answer not in the manual?

iLight SCI0405 Specifications

General IconGeneral
BrandiLight
ModelSCI0405
CategoryController
LanguageEnglish

Related product manuals