Panel reports Zoning fault after configuration
On the SMARTWIRE Panel, all devices on a circuit need the configuration
switches 5,6 & 7 to be the correct setting for the zone they are connected to.
Zone Number Switch 5 Switch 6 Switch 7
1
ON
ON
ON
2 OFF ON ON
3 ON OFF ON
4 OFF OFF ON
5 ON ON OFF
6
OFF
ON
OFF
7 ON OFF OFF
8 OFF OFF OFF
If any device has the wrong setting for the zone it is connected to, the panel
will list it as a zone fault after the configuration has finished.
The panel lets you scroll through any faults, and lights the Flasher or LED of the
currently displayed fault. This makes identifying the device on site easier.
These should be all be corrected and then the panel reconfigured before
proceeding.