28.6 VICTRIX PRO V2 120 EU COMBUSTION FEATURES
Gas ow rates refer to net caloric value at a temperature of 15°C and at a pressure of 1013 mbar.
Flue gas temperature values refer to an air inlet temperature of 15°C and ow/return temperature of 80/60°C.
Methane (G20) LPG (G31)
Maximum heat input of gas G20 m
3
/h 12,12
Min. heat input of gas G20 m
3
/h 1.24
Maximum heat input of gas G31 kg/h 8.89
Min. heat input of gas G31 kg/h 0.91
Supply pressure mbar 20 37
Flue ow rate at maximum nominal heat output kg/h 185 188
Flue ow rate at maximum nominal heat output
gas 20% H2NG
kg/h 192
Flue ow rate at min heat output kg/h 19 20
Flue ow rate at min heat output
gas 20% H2NG
kg/h 20
Chimney losses with burner on (100% Pn) (80/60°C) % (W) 1,8 (2061)
Chimney losses with burner o % (W) 0,02 (19)
Casing losses with burner on (100% Pn) (80/60°C) % (W) 0,1 (114)
Casing losses with burner o % (W) 0,18 (209)
Flue gas temperature Maximum Heat Input °C 71 72
Flue gas temperature Min. Heat Input °C 60 60
CO
2
at Maximum Heat Input % 9.2 10.3
CO
2
at Maximum Heat Input
gas 20% H2NG
% 8,2
CO
2
at Min. Heat Input % 8.9 10.1
CO
2
at Min. Heat Input
gas 20% H2NG
% 7,9
CO at Maximum Heat Input ppm 205 220
CO at Maximum Heat Input
gas 20% H2NG
ppm 95
CO at Min. Heat Input ppm 4 4
CO at Min. Heat Input
gas 20% H2NG
ppm 4
Weighted CO mg/kWh 19 19
NO
x
at the Maximum Heat Input mg/kWh 50 45
NO
x
at Min. Heat Input mg/kWh 14 15
Weighted NO
x
mg/kWh 30 23
NO
x
class - 6 6