TECHNICAL DATA
Error
Code
Anomaly signalled Cause Appliance status / Solution
91
Incorrect ignition
block
e board has exhausted all possible actions in order to ob-
tain optimal ignition of the burner.
Press the Reset button (1)
92
Fan revs correction
limit
e system has exhausted all possible corrections of the
number of fan revs.
e appliance keeps working (1) (2)
93
Combustion signal
beyond limit
e combustion signal is beyond the adjustment range re-
quired for a limited period of time.
e appliance keeps working (1) (2)
94 Combustion anomaly
A problem is detected on the combustion control, which
may be due to: gas low pressure, ue recirculation, defective
gas valve or P.C.B.
If normal conditions are restored, the
appliance restarts without having to
be reset (1) (2)
95
Combustion signal
discontinuous
e system detects a discontinuous combustion signal. e appliance keeps working (1) (2)
96 Clogged ue
is occurs in the event an obstruction is detected in the
ue system.
e appliance does not start (1). If
normal conditions are restored the
boiler restarts without having to be
reset
If error 96 appears aer the Techni-
cian has made changes on the "ue"
parameters, it is necessary to perform
a "quick calibration".
98
Block - maximum no.
of soware errors
e maximum number of soware errors possible has been
reached.
Press the Reset button (1)
99 General block A boiler anomaly has been detected. Press the Reset button (1)
121*
Zone 1 device oine
alarm
Low quality or no radio communication between the zone
1 wireless probe and the concentrator.
Check receiver/sensor positioning
Check probe battery (1)
122*
Zone 2 device oine
alarm
Low quality or no radio communication between the zone
2 wireless probe and the concentrator.
Check receiver/sensor positioning
Check probe battery (1)
123*
Zone 3 device oine
alarm
Low quality or no radio communication between the zone
3 wireless probe and the concentrator.
Check receiver/sensor positioning
Check probe battery (1)
125*
Zone 1 room
temperature probe
anomaly
Faulty room sensor (resistor open or short circuit). Replace room probe (1)
126*
Zone 2 room
temperature probe
anomaly
Faulty room sensor (resistor open or short circuit). Replace room probe (1)
127*
Zone 3 room
temperature probe
anomaly
Faulty room sensor (resistor open or short circuit). Replace room probe (1)
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Service Centre)
(2) e anomaly can only be veried in the list of errors in the “Information” menu