92
INFOSEC UPS SYSTEM 15, rue du Moulin 44880 Sautron France www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 07 19 AA 59 205 03
 it always shows  as output voltage.
  it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.



 it always shows  as output voltage*.
  it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 1 under to represent the output B
voltage.



 it always shows  as output voltage.
  it shows the internal measurement value of the
output C voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 2 under to represent the output C
voltage.

Following table shows LCD display for operating modes and status.
(1) If the UPS is in normal operation, it will show seven screens one by one, which represents 3 phase input
voltages (An, bn, Cn), 3 line input voltages (Ab, bC, CA) and frequency in turns.
(2) If parallel UPS systems are successfully set up, it will show one more screen with “” in parameter 2
and assigned number in parameter 3 as below parallel screen diagram. The master UPS will be default
assigned as ” and slave UPSs will be assigned as either “002” or “003”. The assigned numbers may be
changed dynamically in the operation;


UPS Power
On
Description
When UPS is powered on, it will enter into this mode for a few seconds as
initializing the CPU and system.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E4 Evolution II + 40k TT HV and is the answer not in the manual?

INFOSEC UPS SYSTEM E4 Evolution II + 40k TT HV Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE4 Evolution II + 40k TT HV
CategoryUPS
LanguageEnglish

Related product manuals